Basic Troubleshooting the IMA Drying System

Text Box:

 

DRI HEAT, Home

 

Eliminator

 

VapairVent Ventilation System

 

ITA 75 Drying System

 

IMA 111 Drying System

 

DRI AIR 350-R Drying System 

 

IMA 185 Drying System

 

IMAC 2000S Drying System

 

Eliminator/ELE 6400 & VapairVent Ventilation

Dehumidification Package

 

Drying Systems in Action

 

Typical Drying Set up Using Heat

 

Photo Gallery

 

Heat Drying; an Old Concept

 

As Seen In Cleanfax

 

Heat Drying Structures

 

Create a Drying Chamber

 

Parts & Accessories

 

Air Scrubber/ Negative Air Machine

  

Vortex 5000 Downdraft Fan

 

DuraVent

Blower/Ventilator

 

Mylar Ducting

 

Lay Flat Poly Tubing

 

Select Lay Flat Poly Tubing with FREE SHIPPING

 

Quick Connect Duct System

 

Dry Heat Restoration Supplies

 

Some of the Company's that Use Our Drying System

 

Direct Fired Heaters

 

Indirect Fired Heaters

 

BIO Heaters

 

Contact Us

 

Become A Member of the Emergency Restoration Network

 

 

 

 

 

 

 

 

 

 

 

I turn the main switch to "2" and nothing happens.

1. Has the red reset light illuminated on the burner control box? If yes, press once to reset. The burner will now go through a start up sequence.

2. The maximum thermostat has activated. Press the ▲ and ▼ on the digital thermostat on the front of the control panel.

3. Make sure the thermostat cap is in position (if no room thermostat is simultaneously being used).

4. Make sure the thermostat is set correctly and not sitting directly in the heater airflow.

5. The room thermostat may be defective. Try removing the thermostat and placing the cap on the thermostat connection. If the heater now fires, replace the room thermostat.

6. The capacitor on the burner motor may be defective. Replace if necessary.

7. The fuel pump on the burner may be seized. Remove fuel pump (refer to user manual) and replace if necessary.

The heater starts but no flame is formed.

1. The cut off valve may be closed on the main fuel filter. Open by turning counter-clockwise.

2. The main filter may be clogged. Remove the filter bowl (refer to user manual) and clean the filter if necessary.

3. The filter inside the fuel pump may be clogged. Remove the pump cover (refer to user manual) and clean the filter if necessary.

4. The pump coupling may be defective. Remove the fuel pump from the burner (refer to user manual) and check the pump coupling. The insert should be a D shape. Replace if necessary and remount the fuel pump. NOTE: WHENEVER REMOVING THE FUEL PUMP, ALWAYS MAKE SURE THE CUT OFF VALVE ON THE MAIN FILTER IS CLOSED.

5. The fuel nozzle is blocked or damaged. Remove the burner (refer to user manual) to get to the nozzle. Clean or replace as necessary.

6. The ignition electrodes are faulty or set wrong. Remove the burner (refer to user manual) to check electrodes. Reset, clean or replace as necessary. Settings can be found in the user manual.

7. The magnetic valve does not open. When the burner attempts to fire, a click should be heard right before the flame is formed. If no click, then the valve isn’t opening, allowing fuel to reach the fuel nozzle. Remove the valve and replace if necessary.

8. The main control box is faulty. Remove control box (refer to user manual) and replace if necessary.

The burner starts, a flame is formed, but cuts off after 10-15 seconds, and the red light on the   burner illuminates.

1. The photocell is either dirty or defective. Remove the main control box on the burner (refer to user manual) to get to the photocell. Clean or replace as necessary.

The burner is starting up poorly.

1. There is insufficient air supply to the burner. Check to make sure the air setting is set correctly (refer to user manual for figures). Make sure nothing is blocking the intake grills on either side of the machine (IMAC 2000s). Leave a gap of 1-2 feet for air supply.

2. There could be a problem with the heat exchanger or burner chamber. Remove the burner (refer to user manual) and remove all side panels. Shine a flash light in to the chamber (where the burner was sitting) and look for any light coming through to the outside. Check for any obvious damage to the heat exchanger or combustion chamber. Contact your supplier about changing these if necessary.

The burner is producing soot/smoking.

1. The air intake is set incorrectly. Check the air damper settings on the side of the burner (figures can be found in the user manual). Change if necessary. Note: if machines are being used at high altitude, it may be necessary to open the air damper to compensate. Open the air up until no smoke can be seen.

The burner is running in short bursts.

1. There is too much fuel being used, and the digital thermostat is reaching its limit. This is either due to the pressure being too high at the fuel pump, or the wrong size nozzle being used. Check the pressure at the fuel pump (refer to user manual) and adjust as necessary. Remove the burner (refer to manual) to check the nozzle. Replace if necessary.

The heater can not be switched off.

1. The magnetic valve on the burner is not closing. Turn the fuel supply off at the main filter to stop fuel to the burner. Remove the magnetic valve and replace if necessary.

The heater is producing white smoke.

1. There is air in the fuel supply. This will happen if the machine had previously run out of fuel and is being run for the first time. Usually one cycle will clear this. If not, check for any leaks in the fuel supply line. Replace any if necessary.

The heater stops completely.

1. An overheating problem has occurred and the overheat thermostat has been activated. Reasons for overheating are:     

 A)  The rear end of the heater (where fresh air is drawn in, on the side for the IMA range, or the rear for the  IMACs) is too close to a wall or an obstruction. Leave a clear gap for fresh air to be drawn.      

B)  If using warm air hose off the front off the machine, make sure there isn’t too much back pressure going  back in to the machine (refer to user manual for ratings). Too many bends in the hose WILL cause too much back pressure. Try to keep the hose run as smooth as possible. The same applies if using return air hose.

2.   To reset the digital thermostat and restore power to the burner, press the ▲ and ▼ buttons simultaneously on the digital thermostat on the control panel.

The heater stops completely.

1. An overheating problem has occurred and the overheat thermostat has been activated. Reasons for overheating are:     

 A)  The rear end of the heater (where fresh air is drawn in, on the side for the IMA range, or the rear for the  IMACs) is too close to a wall or an obstruction. Leave a clear gap for fresh air to be drawn.      

B)  If using warm air hose off the front off the machine, make sure there isn’t too much back pressure going  back in to the machine (refer to user manual for ratings). Too many bends in the hose WILL cause too much back pressure. Try to keep the hose run as smooth as possible. The same applies if using return air hose.

2.   To reset the digital thermostat and restore power to the burner, press the ▲ and ▼ buttons simultaneously on the digital thermostat on the control panel.

DRI HEAT Drying Systems

Narrated Step By Step Examples of How the ITA 75

Drying System in Action

Online DRI HEAT Brochure (Printable)

Restoration Packages &  Price List

IMA 61 Drying System (120vac) with

Recirculation

Heat Drying Structures

Learn More About Heat Drying and Drying Classes

Eliminator,

Thermal Evaporative Accelerator

IMA 111 Drying Systems with Recirculation

Typical Drying Setup Using Heat (Printable)

Buy A Drying System

Eliminator Online Brochure

IMA 185 Drying Systems with Recirculation

Create a Drying Chamber

Some of the Company's that Use Our Drying System

Narrated Step By Step Examples of How the Eliminator/ELE 6400

IMAC 2000 Drying System

Parts & Accessories

Previous Customers Comments and Feedback

VapairVent Ventilation System

Heat Drying; an Old Concept

Heater Accessories

Become A Member of the Emergency Restoration Network

ITA 45 Drying Systems

 

As Seen in Cleanfax

BIO Heaters

Contact Us

 

ITA 75 Drying Systems

 

Photo Gallery

Specs & Pricing for Heaters Only

Terms of Use/Disclaimer